Introduction:
    FSE-1000 Series Electro-pneumatic valve positioner are successful products manufactured in accordance with advanced technology introduced from abroad. Fitting out pneumatic control valve, it makes up a closed loop control circuit and transforms current signals output from controller or control system into air signal to actuate the control valve and control the opening level. Meanwhile it feeds back in accordance with the opening level of control valve and can correctly allocate the valve stroke according to the signal output from the system. The positioner could be used for pneumatic actuators with single action and double action, linear stroke and angular stroke.
    FSE-1000 Series Electro-pneumatic valve positioner also can be fit out PTM position transmitter to transform the valve stroke into 4~20 mA DC current position feedback signal. For use in control room. The position transmitter could be directly installed inside wire box of positioner or independently installed outside.
 Features
1. With high vibration resistance (no resonance within the range of 50~200 Hz).
2. The electric interface is multihole and easy to connect in any direction.
3. Easy to adjust and correct. Convenient to transform between normal action and counteraction.
4. For small actuator, vibration could be removed by adjusting the flow of the blowhole.
5. Without changing the parts, it could carry out controlling branch stroke within a half of stroke.
6. Easy to feedback connection.
7. Little in air consumption and good in economy.
 Technology Specifications

Model

FSE -1000L

FSE-1000R

Feedback style

Linear stroke

Angular stroke

Action type

Single action ( S )

Double action ( D ) Single action ( S ) Double action ( D )

Input signal

4~20 mADC , 4~12 mADC , 12~20 mADC ;
0~10 mADC , 0~5 mADC , 5~10 mADC

Air Supply

0.14~0.16 MPa ; 0.17~0.55 MPa

Stroke range

10~150 mm

0~90 o

Input impedance

280 ± 10 Ω (4~20 mADC) ; 950 ± 30 Ω (0~10 mADC)

Air connection

Rc 1/4

Gauge connection

Rc 1/8

Wiring connection

G 1/2

Electrical Safety

Explosion-proof; Intrinsic safety

Ambient temperature

- 40~6 0℃( Intrinsic safety) ; - 20~ 60℃( Explosion-proof)

Relative humidity

5% ~ 100%

Linearity

± 1%

± 2% ± 1% ± 2%

Hysteresis error

≤ 1%

≤ 2% ≤ 1% ≤ 2%

Dead-band

≤ 0.4 %

≤ 0.8 % ≤ 0.4 % ≤ 0.8%

Cam characteristic

Linear ( equal percentage, quick open special oared)

Air consumption

3 L/min ( for single action act. ,supply 0.14 MPa) ;
15 L/min ( for double action act..,supply0.55 MPa)

Flow rate

80 L /min

Position transmitter

Power supply

Vcc 24 V DC

Output signal

4~20 mADC ( twin wire)

Load ability

Resistance : 0~1000 Ω
( including the resistance of signal cable)

Dimension

221 × 166.5 × 117.5 mm

221 × 166.5 × 113.5 mm

Material

Cast aluminium (surface treated)

Weight

2.8 kg

 Code No.
FSE-1000 □ □ □ □ □ □

Feedback style

L

 

 

 

 

 

inear stroke

R

 

 

 

 

 

otating stroke

Action type

 

S

 

 

 

 

ingle action

D

 

 

 

 

ouble action

Electrical Safety

 

m

 

 

 

Ex dm Ⅱ BT6

c

 

 

 

Ex dm II CT6

i

 

 

 

Exia II BT6

N

 

 

 

eather proof type

Feedback Element

 

1

 

 

10~ 40mm ( Linear stroke) ;
M6× 40L ( Rotating stroke)

2

 

 

40~ 70mm ( Linear stroke) ;
M6× 63L ( Rotating stroke)

3

 

 

70~ 100mm ( Linear stroke) ;
M8× 40L ( Rotating stroke)

4

 

 

100~ 130mm ( Linear stroke) ;
M8× 63L (Rotating stroke)

5

 

 

130~ 150mm ( Linear stroke) ;
NAMUR ( Rotating stroke)

Blowhole of pilot valve

 

1

 

0cm 3
The volume of actuator less than 90cm 3

2

 

0~ 180cm 3
The volume of actuator is 90~ 180cm

3

 

80cm 3
The volume of actuator more than 180cm 3

Selective item

 

0

None

1

+PTM ( position transmitter inside)

2

+PTM ( position transmitter outside)

* 3

+L/S ( limit switch inside)

* 4

+L/S ( limit switch outside)

* 5

+PTM+L/S (position transmitter and limit switch inside)

 

* Special order

Feedback module Wiring diagram
Remarks: The poles connection of working power is matching the poles of circuit module.
The signal of output current is series with the input 24V DC.
 Adjustment ways of position transmitter
A. Zero adjusting
    The current increases with turning anticlockwise.
B.Span adjusting
    The current increases with turning clockwise.
C.The requirements could be reached by adjusting the zero and span potentiometers back and forth.